Category:

pair shieded Instrumentation Cables

In Stock

instrument cable are generally used within industrial process manufacturing plants for communication, data and voice transmission signals and
services, Also used for the interconnection of electrical equipment and instruments, typically in petroleum industry.

Category:

Share:

Description

TECHNICAL DATA SHEET OF INSTRUMENT CABLE-Single&Multi Pairs,PE Insulated,Individual&Overall Screened,SWA armoured,PVC Outer Sheath
ITEM DESCRIPTION UNIT DATA
1 Type mm2 12×2×1.5 5×3×1.5 1×2×1.5 1×3×1.5 2×3×1.5 2×2×1.5 4×2×1.5 6×2×1.5
2 Reference standard BS 5308
3 Conductor
Conductor Material Solid copper conductor
Conductor Cross-sectional Area mm2 1.5
Stranding Number No. 1
Approx. Round Conductor Diameter mm 1.38
Max.Conductor D.C. Resistance at 20ºC Ω/KM 12.1
4 Insulation
Material PE
Nominal thickness mm 0.6
5 Individual Screen Aluminum/polyester tape with a 7 strand 0.5mm2 sized tinned annealed Copper drain wire
6 Overall Screen Aluminum/polyester tape with a 7 strand 0.5mm2 sized tinned annealed Copper drain wire
7 Inner sheath
Material PE
Nominal Thickness mm 1.4 1.1 1.0 1.0 1.0 1.0 1.1 1.1
8 Armour layer
Material of armour Galvanized Steel Wire
Nominal diameter of steel wire mm 1.6 1.6 1.25 1.25 1.25 1.25 1.6 1.6
9 Outer sheath
Material Flame Retartant PVC
Nominal thickness mm 1.8 1.6 1.5 1.5 1.5 1.5 1.5 1.5
10 Approx Overall diameter mm 30.3 23.9 13.0 13.4 18.9 17.6 20.5 23.4
11 Approx. Weight kg/km 1969 1187 367 395 645 568 880 1130

flexible cable wire
flexible cable wire

Get In Touch