Category:

6/10KV 6.35/11KV MV Underground Power Cables

In Stock

MV Power Cable is suitable for underground primary residential and commercial distribution circuits. May be used in wet or dry locations, installed in underground ducts, or for direct burial.

Category:

Share:

Description

Application

Their aluminium wire armour (AWA) for single core cables and steel wire armour (SWA) for multicore cables provide robust mechanical protection making these MV cables suitable for direct burial in the ground. These armoured MV mains power cables are more commonly supplied with copper conductors but they are also available with aluminium conductors upon request to the same standard. The copper conductors are stranded (Class 2) whereas the aluminium conductors are compliant to the standard using both stranded and solid (Class 1) constructions.

Operating characteristics

1. Laying temperature: ≥0°C;

2. Cable conductor long-term allowable working temperature: PVC insulated ≤70°C, XLPE insulated ≤90°C;

3. Maximum operating temperature in case of short-circuit: PVC insulated ≤160°C, XLPE insulation ≤ 250°C;

4. Cable bending radius:

 

Item

Single-core Three-core
Non-armored Armored Non-armored Armored
Installation 20D 15D 15D 12D
Close to the terminal and connection box 15D 12D 12D 10D

Note: D is the cable diameter

 

MV Cables Construction

BS6622 BS7835
Conductor Class 2 stranded copper or Class 1 solid /Class 2 stranded aluminium
Conductor Screen Semi-conductive Cross-Linked Polyethylene (XLPE)
Insulation XLPE
Insulation Screen Semi-conductive XLPE
Metallic Screen Individual or overall copper tape
Filler Polyethylene Terephthalate (PET) fibres
Separator Binding Tape
Bedding Polyvinyl Chloride (PVC) Low Smoke Zero Halogen (LSZH) compound
Armour Single core cable: Aluminium Wire Armour (AWA)
Multicore cable: Steel Wire Armour (SWA)
Sheath PVC or Medium Density Polyethylene (MDPE) LSZH

 

Cable models, names, and laying conditions

Model  

Name

 

Laying Occasion

Copper core Aluminum core
YJV YJLV XLPE insulated PVC sheathed power cable  

Laid indoors, and in tunnels and pipelines

YJY YJLY XLPE insulated PE sheathed power cable
YJV22 YJLV22 XLPE insulated steel tape armored PVC sheathed power cable  

Adapt for buried laying, not suitable for in-pipe laying

YJV23 YJLV23 XLPE insulated steel tape armored PE sheathed power cable
YJV32 YJLV32 XLPE insulated thin steel wire armored PVC sheathed power cable  

Laid on riverbeds of rivers or shallow water as connecting lines across rivers or petroleum/natural gas platforms, also  used  in  land high drop areas.

YJV33 YJLV33 XLPE insulated thin steel wire armored PVC sheathed power cable
YJV42 YJLV42 XLPE insulated thick steel wire armored PVC sheathed power cable
YJV43 YJLV43 XLPE insulated thick steel wire armored PE sheathed power cable

Armoured 3-core cable with XLPE insualtion. Rated voltage 6/10 KV 6.35/11KV Cable Data

Conductor  

Insulation thickness (mm)

 

Copper tape screen (approximate) (mm)

 

PVC

bedding thickness (mm)

 

Armored wire outer diameter (mm)

 

Sheath thickness (mm)

 

Outer diameter (approximate) (mm)

 

Copper core cable weight (kg/km)

 

Aluminum core cable weight (kg/km)

Cross sectional area (mm2)  

Structure

Outer diameter (mm)
25 Compact round 6.0 3.4 0.1 1.3 2.5 2.5 48.0 4175 3703
35 Compact round 7.2 3.4 0.1 1.3 2.5 2.6 50.8 4733 4072
50 Compact round 8.4 3.4 0.1 1.4 2.5 2.7 53.8 5491 4547
70 Compact round 10.0 3.4 0.1 1.5 2.5 2.8 57.6 6446 5124
95 Compact round 11.7 3.4 0.1 1.5 2.5 2.9 61.5 7530 5737
120 Compact round 13.1 3.4 0.1 1.6 2.5 3.0 64.9 8628 6363
150 Compact round 14.6 3.4 0.1 1.6 2.5 3.1 68.3 9794 6963
185 Compact round 16.3 3.4 0.1 1.7 2.5 3.3 72.6 11326 7834
240 Compact round 18.5 3.4 0.1 1.8 3.15 3.5 79.2 14268 9737
300 Compact round 20.7 3.4 0.1 1.9 3.15 3.6 84.8 16641 10978
400 Compact round 23.8 3.4 0.1 2.0 3.15 3.9 92.3 20362 12811
500 Compact round 26.6 3.4 0.1 2.1 3.15 4.1 99.3 24203 14764

Get In Touch