15kv 33KV MV Underground Power Cables

In Stock

MV Power Cable is suitable for underground primary residential and commercial distribution circuits. May be used in wet or dry locations, installed in underground ducts, or for direct burial.

Category:

Share:

Description

Application

Their aluminium wire armour (AWA) for single core cables and steel wire armour (SWA) for multicore cables provide robust mechanical protection making these MV cables suitable for direct burial in the ground. These armoured MV mains power cables are more commonly supplied with copper conductors but they are also available with aluminium conductors upon request to the same standard. The copper conductors are stranded (Class 2) whereas the aluminium conductors are compliant to the standard using both stranded and solid (Class 1) constructions.

Operating characteristics

1. Laying temperature: ≥0°C;

2. Cable conductor long-term allowable working temperature: PVC insulated ≤70°C, XLPE insulated ≤90°C;

3. Maximum operating temperature in case of short-circuit: PVC insulated ≤160°C, XLPE insulation ≤ 250°C;

4. Cable bending radius:

 

Item

Single-core Three-core
Non-armored Armored Non-armored Armored
Installation 20D 15D 15D 12D
Close to the terminal and connection box 15D 12D 12D 10D

Note: D is the cable diameter

MV Cables Construction

BS6622 BS7835
Conductor Class 2 stranded copper or Class 1 solid /Class 2 stranded aluminium
Conductor Screen Semi-conductive Cross-Linked Polyethylene (XLPE)
Insulation XLPE
Insulation Screen Semi-conductive XLPE
Metallic Screen Individual or overall copper tape
Filler Polyethylene Terephthalate (PET) fibres
Separator Binding Tape
Bedding Polyvinyl Chloride (PVC) Low Smoke Zero Halogen (LSZH) compound
Armour Single core cable: Aluminium Wire Armour (AWA)
Multicore cable: Steel Wire Armour (SWA)
Sheath PVC or Medium Density Polyethylene (MDPE) LSZH
Rated voltage (kV)
Sectional area (mm2)
No. of core
1st class 0.6/1 1.8/3 3.6/6 6/10 8.7/15 12/20 18/30 21/35
2nd class 1/1 3/3 6/6 8.7/10 12/15 18/20 26/35
1 Core 1.5-800 25-800 25-1200 25-1200 35-1200 50-1200 50-1200 50-1200
2 Core 1.5-185 25-185
3 Core 1.5-400 25-400 25-400 25-400 35-400 50-400 50-400 50-400
4 Core 2.5-400 25-400
5 Core 2.5-400 25-400

 2).  DC resistance: conductor resistance of the finished cable at 20ºC per kilometer is not more than the following values.

Nominal section area (mm2) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800
Copper core 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.099 0.0754 0.0601 0.047 0.0366 0.0283 0.0221
Aluminum core 18.1 12.1 7.41 4.61 3.08 1.91 1.2 0.868 0.641 0.443 0.32 0.253 0.206 0.164 0.125 0.1 0.778 0.0605 0.0469 0.0367

 3). Voltage Test and Partial Discharge Test

Rated voltage Uo (kV)
Item
0.6/1 1.8/3 3.6/6 6/6 6/10 8.7/10 8.7/15 12/20 18/20 18/30 21/35 26/35
Voltage Test voltage 3.5 6.5 12.5 21 30.5 42 63 73.5 91
Test time 5 5 5 5 5 5 5 5 5
Partial discharge test Test voltage 6.2 10.4 15.1 20.8 31.1 36.3 45
Discharge capacity 10 10 10 10 10 10 10